VC Pro VRF 50/60Hz
20
1 Specifications
8-12HP
Table 2-1.1: 8-12HP specifications
HP
8
10
12
Model name
MVC-224WV2GN1
MVC-280WV2GN1
MVC-335WV2GN1
Power supply
V/Ph/Hz
380-415V 3N~50/60HZ
Cooling
1
Capacity
kW
22.4
28.0
33.5
kBtu/h
76.5
95.6
114.4
Power input
kW
5.17
6.81
9.13
EER
4.33
4.11
3.67
Connected
indoor unit
Total capacity
50-130%
Maximum quantity
13
16
20
Compressor
Type
DC inverter
Quantity
1
Oil type
FV 50s
Start-up method
Soft start
Fan
Type
DC
Quantity
1
Motor output
kW
0.56
ESP
Pa
20 default;60 customization option
Airflow rate
m
3
/h
10400
10800
Drive type
Direct
Refrigerant
Type
R410A
Factory charge
kg
8
Pipe
connections
2
Liquid pipe
mm
Ф12.7
Ф15.9
Gas pipe
mm
Ф25.4
Ф28.6
Sound pressure level
3
dB(A)
57
58
60
Net dimensions (W×H×D)
mm
960×1615×765
Packed dimensions (W×H×D)
mm
1025×1790×830
Net weight
kg
188
Gross weight
kg
204
Ambient temp.
Cooling
o
C
-5 to 55
Notes:
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those of the unit's accessories.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VC Pro Series and is the answer not in the manual?

Midea VC Pro Series Specifications

General IconGeneral
BrandMidea
ModelVC Pro Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals