'12 • PAC-T-173
(31) Fan circulator operation (RC-EX1A only)
When the fan is used for circulation, the unit is operated as follows depending on the setting with the remote controller.
1) If the invalid is selected with the remote controller, the fan is operated continuously during the fan operation. (mormal fan
mode)
2) If the valid is selected with the remote controller, the fan is operated or stopped when on the difference of
the remote
controller temperature sensor and the indoor unit return air temperature sensor becomes bigger than 3°C.
(32) The operation judgment is executed every 5 minutes (RC-EX1A only)
Setting temperature is changed according to outdoor temperature
This control is valid with cooling and heating mode. (NOT auto mode)
1) Operate 5 minutes forcedly.
2)
Setting temperature is adjusted every 10 minutes.
(a) Cooling mode.
Ts = outdoor temperature
-
offset value
(b) Heating mode.
Ts = outdoor temperature
-
offset value
3)
If the return air temperature lower then 18°C or return air temperature becomes lower than 25°C, unit goes thermo OFF.
(33) Auto fan speed control (RC-EX1A only)
Inordertoreachtheroomtemperaturetothesettemperatureasquicklyaspossible,theairowrateisincreasedwhentheset
temperature of thermostat differs largely from the return air temperature. According to temperature difference be tureen set
temperature and return air temperature, indoor fan tap are controlled automalically.
・
Auto1:ChangestheindoorunitfantapwithintherangeofHi↔Me↔Lo.
・
Auto2:ChangestheindoorunitfantapwithintherangeofPHi↔Hi↔Me↔Lo.
(34) IU overload alarm (RC-EX1A only)
When the indoor air temperature becomes higher or lower than the temperature set with the remote controller by more than 5 to
10
℃
at 30 minutes after starting operation, the signal is transmitted to the external output (CNT). Receipt of the signal by the
external output is indicated by lighting an LED or other prepared onsite.