Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
None
No display
Stays OFF Stays OFF
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Remote control does not display
anything after the power on.
NO
NO
YES
YES
YES
Is DC10V or
higher detected at remote control connection
terminals?
Is DC10V or higher
detected on remote control wires if
the remote control is
removed?
Are wires
connected properly between the
indoor/outdoor units?
NO
Defective remote control.
Defective remote control.
Defective connecting wire.
Defective remote control
wire. (Short-circuit, etc.)
Defective indoor unit
control PCB
Replace.
2. Error detection method
3 .
Condition of error displayed
4. Presumable cause
Faulty indoor unit control
PCB
Defective remote control
Broken remote control wire
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM80ZS-W and is the answer not in the manual?

Mitsubishi Heavy Industries SCM80ZS-W Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM80ZS-W
CategoryAir Conditioner
LanguageEnglish

Related product manuals