130
-
'19 • SCM-SM-276
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E7
Return air temperature
sensor anomaly
Keeps ashing
1
-
time ash
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
NO
YES
Is the
connection of return
air temperature sensor
connector OK?
Are the
characteristics of return air
temperature sensor
OK?
YES
15
10
5
010304020 50
Temperature-resistance characteristic
Temperature sensor resistance (k)
Temperature (°C)
5k at 25°C
(Broken wire)
(Short-circuit)
Correct.
Connect
connector.
Defective return air
temperature sensor
Replace.
Defective indoor unit
control PCB
Replace.
(Defective return air
temperature sensor input
circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature sensor (Thi-A)
3 .
Condition of error displayed
When the temperature sensor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
Defective return air
temperature sensor connector
Defective return air
temperature sensor
Faulty indoor unit control
PCB
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM80ZS-W and is the answer not in the manual?

Mitsubishi Heavy Industries SCM80ZS-W Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM80ZS-W
CategoryAir Conditioner
LanguageEnglish

Related product manuals