153
-
'19 • SCM-SM-276
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E58
Current safe stop
Keeps ashing
Stays OFF
3
-
time ash
Error code
Remote controller: E58
LED Green Red
Indoor
Outdoor
Content
Current safe stop
(Model SRC50, 60)
Keeps flashing
Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdoor air
temperature sensor
• Defective outdoor unit main
PCB
Diagnosis Countermeasure
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdoor air temperature
sensor.
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor unit main
PCBReplace.
(Defective outdoor air
temperature sensor input
circuit)
Inspect
compressor.
YES
YES
YES
NO
NO
NO
NO
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM80ZS-W and is the answer not in the manual?

Mitsubishi Heavy Industries SCM80ZS-W Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM80ZS-W
CategoryAir Conditioner
LanguageEnglish

Related product manuals