Ye s
Compressor
doesn't operate.
Ye s
Ye s
Is there 230V AC between 3 on the
compressor contactor (52C) and N
on the outdoor terminal block (TB1)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Outdoor fan motor
doesn't operate.
No
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor
capacitor. Refer to 10-3.
Ye s
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB20 on the deicer P.C. board?
Is there 230V AC between L–N on
the outdoor terminal block (TB1)?
Replace the
deicer P.C. board.
Replace the
deicer P.C.
board.
No
No
Ye s
Ye s
No
Check the outdoor fan motor.
Refer to 10-3.
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB 20 on the deicer P.C. board?
Replace the
deicer P.C. board.
No
Ye s
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Is there 230V AC between L–N on
the outdoor terminal block (TB1)?
No
No
+
–
Is there 5V DC between J205 –J101 on
the deicer P.C. board?
+
–
Is there 5V DC between J205 –J101 on
the deicer P.C. board?
w Refer to 10-5.
w
w
w
w
10-4. TROUBLESHOOTING FLOW