6
FUNCTIONS
6.22 High Speed Interrupt Function
6.22.4 Restrictions
6 - 177
1
Overview
2
Performance
Specification
3
Sequence Program
Configuration and
Execution Conditions
4
I/O Nunber Assignment
5
Memories and Files
Handled by CPU Module
6
Functions
7
Communication using
built-in Ethernet ports of
CPU module
8
Communication with
Intelligent Function
Module
(3) Items that have priorities over the high speed interrupt when interrupt is
disabled
(4) Items other than (1) to (3)
(a) Interrupt program setting/fixed scan program setting in PLC parameter
dialog box
If "High speed execution" is selected at the "Interrupt program/fixed scan
execution program setting" section on the "PLC system" tab screen in the "(PLC)
parameter" dialog box of GX Developer, this setting is invalid for the high speed
interrupt function.
(b) High speed buffer transfer
Using the file registers outside the setting range (range in excess of the maximum
number of points) for high speed buffer transfer does not result in an error and
does not transfer data to outside the range. (The contents of the other devices are
not corrupted.)
(c) Precautions for program creation
As in the other interrupt programs, there are the following items as precautions for
program creation. ( Section 3.1.3(7))
Table6.50 Items that hold high speed interrupt by interrupt disable
No. Item Precaution
1 Instruction Interrupt is disabled during instruction execution.
2Link refresh
Interrupt is disabled during refresh (bus access).
For
CC-Link IE controller network, MELSECNET/H, CC-Link or intelligent function module refresh, waiting time
is max. 37.5 s when modules are mounted on main base or max. 40 s when they are mounted on
extension base.
3
Multiple program
execution
When multiple programs are run, interrupt is disabled during program switching. Waiting time is 30 s.
When high speed interrupt function has been set, the recommended number of programs is 1.
4 Monitor
For ladder monitor, device batch-monitor or device entry monitor, waiting time is as follows.
(0.096 number of device points+20) s
5 AC DOWN Waiting time is max. 20ms for high speed interrupt start.

Table of Contents

Other manuals for Mitsubishi Q00JCPU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q00JCPU and is the answer not in the manual?

Mitsubishi Q00JCPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ00JCPU
CategoryController
LanguageEnglish

Related product manuals