© National Instruments | 1-3
RMX Programmable Power Supplies User Manual
Necessary Cable
Vinyl cabtire cable (VCTF): Nominal cross-sectional area 5.5 mm
2
, 3 core
Finished diameter: 10.5 to 14.4 mm in diameter
Rated voltage: 250 V or higher
Input terminal end: 14 mm of insulation stripped from conductor for the L and N wires.
Crimping terminal: (round, M4) that fixes the cable insulation in place
for the GND wire
Length: 3 m or less
Switchboard Breaker Requirements
Installation must be done in accordance with national wiring rules, such as NFPA 70 "NEC"
and CSA C22.1 "CEC".
Rated current: 30 A (for safety, breakers whose rated current exceeds 30 A cannot be used)
Do not power any other equipment from the switchboard breaker.
Keep the breaker readily accessible at all times.
Indicate that the breaker is dedicated for use with this product and that it is used to
disconnect the product from the AC power line.
Figure 1-2. Switchboard Diagram
RMX-4125
Switchboard
N
L
N
L
Breaker indication example
For the
RMX-4125 only
30 A
Power cord
RMX-4125
dedicated breaker

Table of Contents

Other manuals for National Instruments RMX-4120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments RMX-4120 and is the answer not in the manual?

National Instruments RMX-4120 Specifications

General IconGeneral
BrandNational Instruments
ModelRMX-4120
CategoryPower Supply
LanguageEnglish

Related product manuals