Menu advanced has orange text and
is intended for the advanced user. This
menu has a sub-menu.
Menu
2.9
periodic increase
SHULRGLF LQFUHDVH
DFWLYDWHG
SHULRG GD\V
1H[W LQFUHDVH
period
Setting range: 1 - 90 days
Factory setting: activated, 14 days
Menu
2.9.1
To prevent bacterial growth in the water heater, the compressor and the
immersion heater can increase the hot water temperature for a short time
at regular intervals.
The length of time between increases can be selected here. The time can
be set between 1 and 90 days. Factory setting is 14 days. Untick "activated"
to switch off the function.