3-12
Programming 15088:K 3/21/01
Change
Detector
Verification
Time?
Change
Signal Silence
Inhibit Time?
Enable
Detector
Verification
Time?
Enable Signal
Silence Inhibit
Time
Change
Signal Cut-
Out Time?
Enable
Signal Cut-
Out Time?
Enter Detector
Verification
Time (5-50 sec)
Enter Signal Silence
Inhibit Time
(1-255 sec)
Enter Signal Cut-
Out Time
(1-2040 sec)
Yes
Yes
Yes
Yes
Yes Yes
3 = TDLY
(Exit Prog Mode)
No
No
No
No
NoNo
Figure 1-5 Time Delay Option Flow Chart
The following programming example illustrates enabling all three functions:
PRESS@1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM@@@@@ :@3
DO@YOU@WANT@TO@CHANGE@THE@DETECTOR@VERIFICATION@TIME?@(Y=YES,N=NO) :@Y
DO@YOU@WANT@THE@DETECTOR@VERIFICATION@TIME@ENABLED?@(Y=YES,N=NO) :@Y
ENTER@THE@DETECTOR@VERIFICATION@TIME@(5@-@50@IN@1@SECOND@INCREMENTS) :@35
DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@SILENCE@INHIBIT@TIME?@(Y=YES,N=NO) :@Y
DO@YOU@WANT@THE@SIGNAL@SILENCE@INHIBIT@TIME@ENABLED?@(Y=YES,N=NO) :@Y
ENTER@THE@SIGNAL@SILENCE@INHIBIT@TIME@(1@-@255@IN@1@SECOND@INCREMENTS) :@240
DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@CUT-OUT@TIME?@(Y=YES,N=NO) :@Y
DO@YOU@WANT@THE@SIGNAL@CUT-OUT@TIME@ENABLED?@(Y=YES,N=NO) :@Y
ENTER@THE@SIGNAL@CUT-OUT@TIME@(1@-@2040@IN@1@SECOND@INCREMENTS) :@600
Section 1.1.3 Time Delays
D }X1X3X
3=TDLY
Option 3 from the Partial System Programming submenu allows the programmer to enable/disable Alarm
Verification of detectors, Signal-Silence Inhibit and Signal Cut-out for control modules, as well as setting the
appropriate time delays for these functions. For a full description of these functions, see the
Glossary of Terms
and Abbreviations
at the end of this manual.