3-30
Programming 15088:K 3/21/01
Section 1.3 Partial Point Programming
D }X3X
3=PPRG
Option 3 from the Programming Menu allows the programmer to change the operational parameters of SLC Loop
devices, software-defined zones, and annunciator points.
After selecting option 3 from the Main Programming menu, the display will show the Partial Point Programming
submenu:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The Partial Point Programming submenu has six options, where:
1=TYPID Type ID - Changing the Software Type ID of SLC Loop devices, zones and annunciator
points.
2=CBE Control-By-Event - Redefining the Control-By-Event associated with each detector,
module, or zone.
3=LBL Label - Renaming the custom user label for any detector, module, or zone.
4=OPTNS Options - Selecting the optional features associated with any detector or module.
5=AMAP Annunciator Point Mapping - Selecting Annunciator Point Mapping for any detector,
module, or zone.
6=CCBE Cooperative Control-By-Event - Edit the CCBE associated with reverse activated
zones for NOTI•FIRE•NET.
The Partial Point Programming flow chart is located in Figure 1-10. Detailed information on the Partial Point
Programming options follows.
NOTE
Each option under Partial Point Programming prompts the programmer to enter the address of the
detector, module, zone, or annunciator point to be affected. Leading zeros are not required. The
address assumes the following format:
LXX(D/M)YY (for devices) or ZXXX (for zones) or AXXPYY (for annunciator points)
Example: For the 44th module on SLC Loop 3, enter L3M44
Annunciator
Module 1 to 32
Annunciator
Point 1 to 64
SLC Loop
1 to 10 (AM2020),
1 to 4 (AFP1010)
Addressable Detector or Mod-
ule followed by an address in
the range 1 to 99
Software-defined
Zone Z1 to Z240