ID50 Series Panel - Operating Manual
Operator Actions at Panel
13 997-264-000-8, Issue 8
January 2007
4.1.2 Internal Buzzer
The panel has an internal buzzer which gives a local
warning when any of the following is detected:
a. Fire condition.
b. Pre-alarm condition.
c. Fault condition.
4.1.3 Access Codes
With the exception of the Loop Booster Output Test option,
the actions described in this manual require access Level 2,
which is invoked either by turning the keyswitch or by entry
of an access code. The access code is a sequence of
numbers configured in the panel during commissioning. The
panel has two levels of access codes:7 Level 2 and Level
3. Level 3 is required for testing the loop booster output and
for panel configuration and commissioning procedures.
The panel has a maximum of ten (10) Level 2 access
codes, each defined by the user identification number
[U0 - U9] in the top left-hand corner. Entering a Level 2
access code allows access to all functional controls and
some system operation parameters. (Operating the
keyswitch to enter Level 2 always displays ‘[U9]’).
Note: When the panel is at Level 3, [S1] is displayed in
place of the user identification number.
1 Press the ‘ button at the ‘Status: NORMAL
message to prompt for a Level 2/3 access code, as
shown below:
2 Press and hold the ‘
0..9
’ button while pressing the
appropriate 4 digit Level 2 access code. ‘*’ will appear
on the LCD as the numbers are entered.
3 Press the ‘
5
’ button to confirm the entered code.
The Level 2 Options are then displayed.
4 The procedure to cancel Level 2 (and thus prevent
any other person accessing Level 2 options) is given
in Section 4.1.1).
Note: If an incorrect access code is entered, the following
is displayed:
Press the ‘
4
’ button or wait for approximately one
minute to return to the ‘Status: NORMAL’ message.
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
[U0] 1:Test 2:Disable/Enable 3:Clock
4:View Mode 5:Commission
ERROR - INCORRECT PASSCODE ! ! !
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode:
* * * *
< : BackSp
Throughout this manual a
U accompanied by a
number represents a Level
2 access code.
5
1
2,3
Operations within this
manual require Level 2
access (code or keyswitch),
although a Level 3 access
code may be entered.

Questions and Answers: