INA 15092:I 05/30/01
59
SECTION 2 THE MAIN PROGRAMMING MENU
The Programming Mode is accessed by entering the following (a Level Two password is required):
D } X
After entering the Programming Mode, the display will show the following Main Programming menu:
PRESS 1=PSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG :
The Main Programming menu has six options shown below. NOTE: Option 2 of the Main Programming menu is reserved
for future use.
1=PSYS Partial System Programming - Selective programming of INA functions
3=PPRG Partial Point Programming - Selectively altering the operating parameters of annunciator
points.
4=FPRG Full Point Programming - Complete programming of annunciator points and their
respective operating parameters.
5= REMV Remove - Permits the selective removal (from INA memory) of any of the annunciator
points.
6=PSWD Password - Allows the programmer to assign custom five-digit Level One and Level Two
passwords.
7=MSG Message - Allows the Level Two programmer to define the custom 40-Character User Label
displayed on the CRT Monitor and the INA's Liquid Crystal Display (LCD).
Refer to Figure 2.0-1 for a flow chart of the Main Programming menu. Detailed information on the Main Programming
Options follows.