EasyManua.ls Logo

Notifier NFS-320 - 3.8 Pre-Alarm Warning Mode of Operation

Notifier NFS-320
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Installation NAC Connections and Releasing Circuits
3.6 NAC Connections and Releasing Circuits
The control panel provides four NAC terminals as shown in Figure 3.9. Each can be configured as
Style Y (Class B) or Style Z (Class A) as shown in Figure 3.8. Each circuit can provide 1.5 A of
current, but the total current drawn from the main power supply cannot exceed 7.4 A in alarm
condition (refer to Table A.2). Additionally, TB2 (on CPS-24), TB10 and all 4 NACs share a
maximum of 3.0 A in standby and 6.0 A in alarm. NAC circuits are supervised and power-limited.
Use UL-listed 24 VDC notification appliances only (refer to the Device Compatibility Document).
nfs640-nacout.cdr
Style Y (Class B)
Connection
Style Z (Class A)
Connection
Unused Circuits
UL-listed ELR-2.2K,
1/2 W (supplied)
Figure 3.8 Notification Appliance Circuit (NAC)
Connections
Figure 3.9 NAC Terminals and NAC LEDs
TB9 - NAC#1
TB8 - NAC#2
TB7 - NAC#3
TB6 - NAC#4
CPU-320-NACS.wmf
A–
A–
A–
A–
A+
A+
A+
A+
B–
B–
B–
B–
B+
B+
B+
B+
NOTE: Any NAC can be programmed as a releasing circuit, and the releasing circuit must
be supervised; For more information, refer to Section 4.7 “Releasing Applications” in this manual
and the NFS-320/E/C Programming Manual. Refer to the Device Compatibility Document for UL-
listed compatible releasing devices. Sample connections for NAC terminals are shown in
Figure 3.8. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part
of Step 4.

Table of Contents

Other manuals for Notifier NFS-320

Related product manuals