EasyManuals Logo
Home>Omron>Controller>C200HX Series

Omron C200HX Series User Manual

Omron C200HX Series
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #125 background imageLoading...
Page #125 background image
113
Appendix B
Specifications
The following figures and tables provide specifications for each Unit of the C200HX/C200HG/C200HE. I/O Units
may take on one of two different shapes and are sometimes referred to as A-shape Units or B-shape Units.
Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape
Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of
these two shapes of I/O Unit.
General Specifications
Item Specifications
Power Supply
Unit
C200HW-PA204 C200HW-PA204S C200HW-PA204R C200H-PA209R C200HW-PD024
Supply voltage 100 to 120 VAC/200 to 240 VAC (50/60 Hz) 24 VDC
Operating voltage
range
85 to 132 VAC/170 to 264 VAC 19.2 to 28.8 VDC
Power
consumption
120 VA max. 180 VA max. 40 W max.
Inrush current 30 A max. 30 A max. at 100
to 120 VAC
40 A at 200 to
240 VAC
30 A max.
Output capacity
5 VDC, 4.6 A (including power supply to the CPU Unit) 5 VDC, 9 A
(including power
supply to the CPU
Unit)
5 VDC, 4.6 A
(including power
supply to the CPU
Unit)
26 VDC, 0.625 A
Total: 30 W
26 VDC, 0.625 A
24 VDC, 0.8 A
Total: 30 W
26 VDC, 0.625 A
Total: 30 W
26 VDC, 1.3 A
Total: 45 W
26 VDC, 0.625 A
Total: 30 W
Output terminals Without With
(see note 1)
Without Without
RUN output
(see note 5)
Without SPST-NO contact
Switching
capacity:
2 A at 250 VAC
(resistive load),
0.5 A at 250 VAC
(inductive load),
2 A at 24 VDC
SPST-NO contact
Switching
capacity:
2 A at 240 VAC
(resistive load),
0.5 A at 120 VAC
(inductive load),
2 A at 24 VDC
(resistive load), 2
A at 24 VDC
(inductive load)
Without
Insulation
resistance
AC: 20 M min. (at 500 VDC) between external terminals and GR terminal
(see note 2)
DC: 20 M min.
(at 500 VDC)
between external
terminals and GR
terminal (see note
2)
Dielectric strength
AC: 2,300 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
DC: 2,300 VAC,
50/60 Hz for 1
minute between
external terminals
DC: 1,000 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
external
terminals
and GR terminals
with a leakage
current of 10 mA
max. (see note 2)

Table of Contents

Other manuals for Omron C200HX Series