• If the control mode is 2-PID with fuzzy self-tuning, the
parameters
p
,
i
, d
, or
ofr
will not be displayed (i.e., there is no
need
to set these parameters). Fuzzy self-tuning always adjusts
all PID constants to optimum values inside the Temperature
Controller.
Proportional
Band:
p
When
the character “
p
” is displayed on the PV display
, the propor
-
tional band (P constant) can be changed using the Up and Down
Keys.
The new
value will be displayed on the SV display
. It can be
set
in a
range from 0.1
°
to 999.9
°C/°
F in units of 0.1
°C/°F
. The value
is factory-set to 8.0
°C/°F
. However
, the E5
j
J-F (Fahrenheit Model)
is
factory-set to 14.4
°F.
Integral T
ime :
i
When
the character “
i
” is displayed on the PV display
, the integral
time (I constant) can be changed using the Up and Down Keys. It
can
be set in a range from 0 to 3,999 seconds in units of 1 second.
The
value is factory-set to 233 seconds.
Derivative T
ime :
d
When
the character “
d
” is displayed on the PV display
, the deriva
-
tive
time (D constant) can be
changed using the Up and Down Keys.
It
can be set in a range from 0 to 3,999 seconds in units of 1 second.
The
value is factory-set to 40 seconds.
Manual Reset V
alue Setting (%) :
ofr
The
necessary output value in stable state will be set within a range
of
0.0% to 100.0%. The output value is factory-set to 50.0%. In P
or
PD
mode
(i.e., when I is 0), the T
emperature Controller will be bal
-
anced
with a deviation value between the
set point and process val
-
ue. This deviation value is called the
of
fset. By changing the manual
reset
value, the of
fset can be eliminated.
Engineering Level Parameters
The value set before shipping
appears.
(see note 1)
Displayed
if the E5
j
J with a com
-
munications
function is used.
(Data bit length setting)
(Parity check setting)
(Stop bit length setting)
Displayed
if the E5
j
J is in 2-PID
opera
-
tion
with fuzzy self-tuning.
(Stable
range setting)
Displayed
if the E5
j
J is in 2-PID opera
-
tion.
(Alpha
setting)
(Automatic return of display mode)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Standby sequence
reset
method
setting)
(Input
shift display selection)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Alarm 1 hysteresis
setting)
Displayed if the E5jJ with an alarm
function
is used (see note 2).
(Alarm 2 hysteresis
setting)
(Set
point lower limit setting)
(Set point upper limit setting)
Displayed if the E5jJ with
event
input 2 is used.
(Event input 2 function
selection)
Note: 1. The
E5
jJ-jjjj
-F values set before shipping
are
dif
ferent. Refer to the
E5
j
J Operation Manu
-
al
(Z103).
2. The
value will
not be displayed if the alarm mode
switch
is set to 0 or if the E5
j
J does not incorpo
-
rate
any alarm.
(°C/°
F selection)
15.0