SECTION 6 Communications Data for Modbus
6-12
Address Parameter name Setting (monitor) value Level
1006 Automatic display return
time
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
Advanced
function
setting
1010 Additional PV display H'00000000 (0): OFF
H'00000001 (1): ON
1016 MV display H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)
1018 Protect level move time H'00000001 to H'0000001E (1 to 30)
101A PV change color H'00000000 (0): ORG
H'00000001 (1): RED
H'00000002 (2): GRN
H'00000003 (3): R-G
H'00000004 (4): G-R
H'00000005 (5): R-G.R
H'00000006 (6): G-O.R
H'00000007 (7): O-G.R
101C PV stable band H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt multi-input models)
(0.01 to 99.99 for Analog input models)
101E Additional auto/manual
display switch
H'00000000 (0): OFF
H'00000001 (1): ON
1020 Display character switch H'00000000 (0): OFF
H'00000001 (1): ON
1100 Protocol setting
(See note 3.)
H'00000000 (0): CompoWay/F (SYSWAY)
H'00000001 (1): Modbus
Commu-
nications
setting
1102 Communications unit
number (See note 3.)
H'00000000 to H'00000063 (0 to 99)
1104 Communications baud
rate (See note 3.)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
1106 Communications data
length (See note 3.)
H'00000007 (7): 7
H'00000008 (8): 8
1108 Communications ttop bits
(See note 3.)
H'00000001 (1): 1
H'00000002 (2): 2
110A Communications parity
(See note 3.)
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
110C Send data wait time
(See note 3.)
H'00000000 to H'00000063 (0 to 99)