6.1 Variable Area (Setting Range) List
6-13
Note 1. Not displayed on the Controller display.
Note 2. The parameter will not be shown on the Controller display when alarm 3 is not assigned to an
output.
Note 3. After communications parameters have been changed, they are enabled by resetting the
Controller.
130A Cold junction compensa-
tion method
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
1314 α H'00000000 to H'00000064 (0.00 to 1.00)
1328 Heater burnout latch H'00000000 (0): OFF
H'00000001 (1): ON
132A Heater burnout hystere-
sis
H'00000001 to H'000001F4 (0.1 to 50.0)
132C HS alarm latch H'00000000 (0): OFF
H'00000001 (1): ON
132E HS alarm hysteresis H'00000001 to H'000001F4 (0.1 to 50.0)
1334 Number of multi-SP uses H'00000000 (0): No multi-SP
H'00000001 (1): 2SP
H'00000002 (2): 4SP
Advanced
function
setting
1336 Multi-SP usage H'00000000 (0): OFF
H'00000001 (1): ON
1338 HB ON/OFF H'00000000 (0): OFF
H'00000001 (1): ON
133A MB command logic
switching (See note 7.)
H'00000000 (0): OFF
H'00000001 (1): ON
133C Input error output H'00000000 (0): OFF
H'00000001 (1): ON
133E Input shift type H'00000000 (0): 1-point shift
H'00000001 (1): 2-point shift
1340 Output status during
error
H'00000000 (0): 0 mA
H'00000001 (1): MV at PV error
1342 ST stable range H'00000001 to H'0000270F (0.1 to 999.9)
1344 RT H'00000000 (0): OFF
H'00000001 (1): ON
1346 HS alarm H'00000000 (0): OFF
H'00000001 (1): ON
1348 LBA detection time H'00000000 to H'0000270F (0 to 9999)
134A LBA level H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt multi-input models)
(0.01 to 99.99 for Analog input models)
134C LBA band H'00000000 to H'0000270F
(0.0 to 999.9 for TC/Pt multi-input models)
(0.00 to 99.99 for Analog input models)
134E Soak time units H'00000000 (0): Minutes
H'00000001 (1): Hours
1350 Alarm SP selection H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
Address Parameter name Setting (monitor) value Level