SECTION 6 Communications Data for Modbus
6-4
Address Parameter name Setting (monitor) value Level
0600 Manual manipulated vari-
able
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling: H'FFFFFBE6 to H'0000041A (−105.0 to
105.0)
Operating
0602 Set point SP lower limit to SP upper limit
0608 Heater current 1 value
monitor
H'00000000 to H'00000226 (0.0 to 55.0)
060A MV monitor (heating) Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling: H'00000000 to H'0000041A (0.0 to
105.0)
060C MV monitor (cooling) H'00000000 to H'0000041A (0.0 to 105.0)
0700 Cooling coefficient H'00000001 to H'0000270F (0.01 to 99.99) Adjust-
ment
0708 Dead band H'FFFFF831 to H'0000270F
(−199.9 to 999.9 for TC/Pt multi-input models)
(−19.99 to 99.99 for Analog input models)
070A Manual reset value H'00000000 to H'000003E8 (0.0 to 100.0)
070C Hysteresis (heating) H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt multi-input models)
(0.01 to 99.99 for Analog input models)
070E Hysteresis (cooling) H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt multi-input models)
(0.01 to 99.99 for Analog input models)
0710 Control period (heat) H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
Initial set-
ting
0712 Control period (cool) H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
0718 SP ramp time unit H'00000000 (0): EU/second
H'00000001 (1): EU/minute
Advanced
function
setting
071A SP ramp set value H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
Adjust-
ment
071E MV at stop Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling: H'FFFFFBE6 to H'0000041A (−105.0 to
105.0)
0722 MV at PV error Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling: H'FFFFFBE6to H'0000041A (−105.0 to
105.0)
072C Lower-limit temperature
input shift value
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
0730 Upper-limit temperature
input shift value
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
0734 Heater current 1 value
monitor
H'00000000 to H'00000226 (0.0 to 55.0) Operating
0736 Heater burnout detec-
tion 1
H'00000000 to H'000001F4 (0.0 to 50.0) Adjust-
ment
0738 Leakage current value 1
monitor
H'00000000 to H'00000226 (0.0 to 55.0) Operating