6.1 Variable Area (Setting Range) List
6-7
Note 1. The input type can be selected to match the connected sensor.
There are two input type specifications: Thermocouple/Resistance thermometer input and
Analog input.
Note 2. The alarm function can also be used in Controllers without alarm output terminals. In this case,
confirm alarm occurrences via the status data.
0C00 Input type (TC/Pt multi-
input models) (See note.)
H'00000000 (0): Pt (−200 to 850°C/−300 to 1500°F)
H'00000001 (1): Pt (−199.9 to 500.0°C/−199.9 to 900.0°F)
H'00000002 (2): Pt (0.0 to 100.0°C/0.0 to 210.0
°F
)
H'00000003 (3): JPt (−199.9 to 500.0°C/−199.9 to 900.0°F)
H'00000004 (4): JPt (0.0 to 100.0°C/0.0 to 210.0
°F
)
Initial set-
ting
H'00000005 (5): K (−200 to 1300°C/−300 to 2300°F)
H'00000006 (6): K (−20.0 to 500.0°C/0.0 to 900.0°F)
H'00000007 (7): J (−100 to 850°C/−100 to 1500°F)
H'00000008 (8): J (−20.0 to 400.0°C/0.0 to 750.0°F)
H'00000009 (9): T (−200 to 400°C/−300 to 700°F)
H'0000000A (10): T (−199.9 to 400.0°C/−199.9 to 700.0°F)
H'0000000B (11): E (0 to 600°C/0 to 1100°F)
H'0000000C (12): L (−100 to 850°C/−100 to 1500°F)
H'0000000D (13): U (−200 to 400°C/−300 to 700°F)
H'0000000E (14): U (−199.9 to 400.0°C/−199.9 to 700.0°F)
H'0000000F (15): N (−200 to 1300°C/−300 to 2300°F)
H'00000010 (16): R (0 to 1700°C/0 to 3000°F)
H'00000011 (17): S (0 to 1700°C/0 to 3000°F)
H'00000012 (18): B (100 to 1800°C/300 to 3200°F)
H'00000013 (19): Infrared temperature sensor (K 140°F/
60°C)
0C00 Input type (TC/Pt multi-
input models) (See note.)
H'00000014 (20): Infrared temperature sensor
(K 240°F/120°C)
H'00000015 (21): Infrared temperature sensor
(K 280°F/140°C)
H'00000016 (22): Infrared temperature sensor
(K 440°F/220°C)
H'00000017 (23): 0 to 50 mV
Initial set-
ting
Input type (Analog input
models, see note)
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
H'00000002 (2): 1 to 5 V
H'00000003 (3): 0 to 5 V
H'00000004 (4): 0 to 10 V
0C02 Temperature unit H'00000000 (0): °C
H'00000001 (1): °F
0C12 Scaling lower limit H’FFFFF831 to scaling upper limit −1
(−1999 to scaling upper limit −1)
0C16 Scaling upper limit Scaling lower limit +1 to H’0000270F
(Scaling lower limit +1 to 9999)
0C18 Decimal point position
(TC/Pt multi-input mod-
els)
H'00000000 to 00000001 (0 to 1)
Decimal point position
(Analog input models)
H'00000000 to 00000003 (0 to 3)
Address Parameter name Setting (monitor) value Level