EasyManuals Logo
Home>Omron>Timer>H5CN

Omron H5CN User Manual

Omron H5CN
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #125 background imageLoading...
Page #125 background image
New H3Y
New H3Y
125
Characteristics
Accuracy of operating time
!
1% FS max. (0.5 s range:
!
1%
!
10 ms max.)
Setting error (see note 1)
!
10%
!
50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Reset voltage 10% max. of rated supply voltage
Influence of voltage (see note 1)
!
2% FS max.
Influence of temperature (see note
1)
!
2% FS max.
Insulation resistance 100 M
$
min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed
non-current-carrying metal parts) (see note 2)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) (see note
2)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) (see note 2)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Shock resistance Destruction: 1,000 m/s
2
(approx. 100G)
Malfunction: 100 m/s
2
(approx. 10G)
Ambient temperature Operating: --10
"
Cto50
"
C (with no icing)
Storage: --25
"
Cto65
"
C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y-2: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)
H3Y-4: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h)
Impulse withstand voltage Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC
Noise immunity
!
1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1
&
s, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Enclosure rating IP40
Weight Approx. 50 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to
1GHz)(level3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL508, CSA C22.2 No. 14
Conforms to VDE0435/P2021, VDE0110 (for in-panel use)
Conforms to EN50081-2, EN50082-2
Note: 1. Add
!
10 mS to the above value for the 0.5-S range model.
2. Terminal screw sections are excluded.

Other manuals for Omron H5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron H5CN and is the answer not in the manual?

Omron H5CN Specifications

General IconGeneral
BrandOmron
ModelH5CN
CategoryTimer
LanguageEnglish

Related product manuals