5 Modbus Connection
5-4
NB-series Programmable Terminals Host Connection Manual (V108)
5-3 Communication Parameter Setting
When Using Modbus RTU Protocol
PT default communication parameters: 9600bps (Baud Rate), 8 (Data Bit), even (Parity Check), 1 (Stop
Bit) and 1 (PLC Station No.)
Note 1 Modbus RTU driver supports little-endian. Modbus RTU Modicon_BE supports big-endian.
When Using Modbus RTU Extend Protocol
PT default communication parameters: 9600bps (Baud Rate), 8 (Data Bit), even (Parity Check), 1 (Stop
Bit) and 1 (PLC Station No.)
PT Settings