7 Analog Output Units
7 - 4
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
z 1/8000 Resolution
The output set value of the signed integer value (0 to 8000) is converted to currents from 4 to 20 mA
and output.
The output set value range for which conversion is possible is the signed integer (-400 to +8400)
and for this case the output voltage becomes from 3.2 to 20.8 mA.
z 1/30000 Resolution
The output set value of the signed integer (0 to 30000) is converted to current from 4 to 20 mA and
output.
The output set value range for which conversion is possible is the signed integer (-1500 to +31500)
and for this case the output voltage becomes from 3.2 to 20.8 mA.
Output Range: 4 to 20 mA
−
32768
Output set value
(decimal)
Current
−
4
00
4 mA
0 mA
3.2 mA
20.8 mA
20 mA
32767
08000
8400
Fixed at the lower limit
in this range.
Fixed at the upper limit
in this range.
−
32768
Output set value
(decimal)
Current
−
15
00 30000
31500
4 mA
0 mA
3.2 mA
20.8 mA
20 mA
32767
0
Fixed at the lower limit
in this range.
Fixed at the upper limit
in this range.