7 Analog Output Units
7 - 20
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
This function corrects offsets in the output voltages and output currents that occur due to the deteriora-
tion of the NX Units and calibrate the Units again.
You can use this function to calibrate the equipment that requires the periodic calibration.
This function corrects the converted values of output voltages and output currents at 2 points, 0% and
100%, as shown in the figure below.
The calibration result is saved in the NX Unit.
z Calibration Example 1
z Calibration Example 2
7-5-5 User Calibration
Purpose
Details on the Function
0%
100%
Output set value
Before
correction
After
correction
Voltage/current
0%
100%
Output set value
Before
correction
After
correction
Voltage/current