7 - 7
7 Analog Output Units
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
7-4 List of Settings
7
*2. The descriptions of Chîš… Hold Value Setting are as follows.
z Four-point Output Units
Set value Setting description
0 Hold Last State
1Low Limit
2 High Limit
3 User Count
4 Zero Count
Setting name Description
Default
value
Setting
range
Unit Index
Subin-
dex
Refer-
ence
Ch1 Enable/Disable Set to enable or disable
the channel.
FALSE: Disable
TRUE: Enable
TRUE TRUE or
FALSE
--- 5010
hex
01 hex P. 7-10
Ch2 Enable/Disable TRUE TRUE or
FALSE
--- 02 hex
Ch3 Enable/Disable TRUE TRUE or
FALSE
--- 03 hex
Ch4 Enable/Disable TRUE TRUE or
FALSE
--- 04 hex
Ch1 Range Setting Set the range.
0: 4 to 20 mA
1: 0 to 10 V
2: -10 to +10 V
3: 0 to 5 V
4: 1 to 5 V
5: 0 to 20 mA
*1 *1
--- 5011
hex
01 hex P. 7-3
Ch2 Range Setting
*1 *1
--- 02 hex
Ch3 Range Setting
*1 *1
--- 03 hex
Ch4 Range Setting
*1 *1
--- 04 hex
Ch1 Hold Value Setting Set the value to output at
load OFF.
4
0 to 4
*2
--- 5012
hex
01 hex P. 7-14
Ch1 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0 -32768 to
32767
--- 02 hex
Ch2 Hold Value Setting Set the value to output at
load OFF.
4
0 to 4
*2
--- 03 hex
Ch2 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0 -32768 to
32767
--- 04 hex
Ch3 Hold Value Setting Set the value to output at
load OFF.
4
0 to 4
*2
--- 5012
hex
05 hex P. 7-14
Ch3 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0 -32768 to
32767
--- 06 hex
Ch4 Hold Value Setting Set the value to output at
load OFF.
4
0 to 4
*2
--- 07 hex
Ch4 User-specified
Value Setting
Set the value to output
when the Load OFF Out-
put Setting is set to output
the user specified value.
0 -32768 to
32767
--- 08 hex