EasyManuals Logo
Home>Omron>I/O Systems>NX-AD series

Omron NX-AD series User Manual

Omron NX-AD series
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
A - 17
Appendices
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-1 Data Sheet
A
A-1-2 Analog Input Units
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3608
Number of points
4 points
External connection
terminals
Screwless clamping terminal block (12 ter-
minals)
I/O refreshing method
Switching synchronous I/O refreshing and Free-Run refreshing
Indicators
TS indicator
Input method
Differential input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 M min.
Resolution
1/30000 (full scale)
Overall
accuracy
25
°
C
±0.1% (full scale)
0
to
55
°
C
±0.2% (full scale)
Conversion time
10 μs/point
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 M min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power con-
sumption
Connected to a CPU Unit
1.45 W max.
Connected to a Communications Cou-
pler Unit
1.10 W max.
Current consumption
from I/O power supply
No consumption
Weight
70 g max.
Circuit layout
Installation orienta-
tion and restrictions
Installation orientation:
Connected to a CPU Unit
Possible in upright installation.
Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
Terminal connection
diagram
Input disconnection
detection
Not supported.
AMP
AG
AG
Input1+ to 4+
Terminal block
Input1
to 4
510 KΩ
510 KΩ
AG: Analog circuit
internal GND
NX bus
connector
(left)
I/O power supply +
I/O power supply
I/O power supply +
I/O power supply
NX bus
connector
(right)
AG
A1 B1
A8 B8
AG
AG
AG
AG terminal is connected to 0 V of analog circuit inside the Unit.
It is not necessary to wire AG terminal normally.
Input +
Input
Input1+
Voltage Input Unit
NX-AD3608
Input1
Input2+
Input2
Input3+
Input3
Input4+
Input4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX-AD series and is the answer not in the manual?

Omron NX-AD series Specifications

General IconGeneral
BrandOmron
ModelNX-AD series
CategoryI/O Systems
LanguageEnglish

Related product manuals