IG-183-EN version 06; 31/03/2020
87
General instructions
cgm.3 system: medium voltage SF
6
gas-insulated
cubicles up to 38 kV according to IEEE and CSA standards
Contents
9. Environmental information
cgm.3 cubicles are dened as a sealed, pressurized system
which contains sulfur hexauoride (SF
6
).
SF
6
is included in the Kyoto Protocol list of greenhouse gases.
SF
6
has a GWP (Global Warming Potential) of 22 200 units.
(TAR, IPCC 2001)
At the end of the product’s life, the SF
6
contained in it
must be recovered for processing and recycling, to prevent
it being released into the atmosphere. Extracting and
handling of SF
6
must be carried out by qualied personnel,
using a sealed piercing system.
For the usage and handling of the SF
6
, the indications listed
in IEC 62271-303 must be followed.
The management and treatment of the rest of materials
must be carried out in accordance with the countrys
current legislation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ormazabal cgm.3 Series and is the answer not in the manual?

Ormazabal cgm.3 Series Specifications

General IconGeneral
BrandOrmazabal
Modelcgm.3 Series
CategoryPower distribution unit
LanguageEnglish

Related product manuals