47
13 Protection Control
13.1. Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature and compressor OFF temperature during the period.
This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting current Control
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
The reason of the difference is to reduce the starting current flow.
13.5. Freeze Preventive Control
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more than 4 minutes.
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature
reaches certain temperature for 5 sec. the speed will be increased as in below figure.
Compressor will turn off when indoor temperature falls below 2°C for more than 4 minutes. It will restart again when indoor heat
exchanger temperature rises to 10°C.
Restart control (Time Delay Safety Control) will be applied in this control.

Table of Contents

Other manuals for Panasonic CS-A9HKD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A9HKD and is the answer not in the manual?

Panasonic CS-A9HKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-A9HKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals