13.11 Outdoor Fan Motor Control
When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
This is to release the heat and to obtain the lowest pressure as fast as possible.
13.12 Hot Start Control
Hot start control is to prevent cool air discharge into room when heating operating starts.
Hot start is executed after heating operation starts and deice operation is completed.
Indoor fan control during hot start is shown below:
Indoor Pipe Temperature Indoor Fan
30°C OFF
30°C < t 34°C SLo
t 34°C Lo-
When indoor pipe temperature over 34°C or maximum 40 minutes, hot start is completed.
During hot start and for hot start completed, intake thermostat is ignored and no Thermo OFF.
13.13 Cold Draft Prevention Control
This operation is to prevent the Cold Draft during Heating mode operation.
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor
heat exchanger temperature as shown below:
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
Anti Cold Draft Control will stop when:
o Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
o 30 Minutes Time Save Control activates.