Page 14 Connections
Figure 3: CVT485 Connection
Using an External Power Input
When an external power input is used as a backup power supply,
or when the power lines of a RS485 adapter module (CVT485) are
used to power the PCS250, the following connections are
required:
Screw 1 = +12V
•Screw 2 = ground
The maximum wire length for each of those power lines is as
follows:
12m (40 ft.) for AWG24
20m (65 ft.) for AWG22
30m (100 ft.) for AWG20
50m (160 ft.) for AWG18
+ -
A+ B-
+ -
12 VDC
A+ B-
RS485
PCS250
GPRS14
Control Panel
CVT485
VDMP3
Up to 300m (1000 ft.)
* Up to 50m (160 ft.) AWG18
* or use an independent power source for the PCS250