Compax3 device description
Function of the LEDs on the front panel
20 192-120102 N7 - February 2004
Caution!
When the control voltage is missing there is no indication whether or
not high voltage supply is available.
3.2.1. Function of the LEDs on the front panel
State LED red LED green
Voltages missing off off
While booting alternately flashing
! No configuration present.
! SinCos feedback not detected.
! IEC program not compatible with the
firmware.
! For F12: Hall signals invalid.
flashing off
Axis without current excitation off Flashes slowly
Power supplied to axis; commutation calibration
running
off Flashes quickly
Axis with current excitation off on
Axis in fault status / fault present on off
3.2.2. Power supply plug X1 for 230VAC devices
PIN Description
1
L
2N
3PE
Mains connection: Compax3 S0xx V2
Controller type S025 V2 S063 V2
Mains voltage
Single phase 230VAC + 10%
80-230VAC+10% / 50-60Hz
Rated input current
6Aeff 16Aeff
Maximum fuse rating per device
10A (automatic circuit
breaker K)
16 A (automatic circuit
breaker K)
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after
switching off the power supply!