Technical Specifications
Environmental Specifications
Ambient temperature: 32~140 (0~60 °C)
Protection class: IP66
Vibration resistance parameter: 100Hz
Electrical Specifications
Connections: cable gland
Supply voltage:
24 V DC ± 10 %, ≥1A. Recommend switching-mode power supply.
Power input: <5W
Input resistance for set-point signal: 12
Analog output signal: maximum load 560Ω
Mechanical Specifications
Cover material: Polycarbonate (PC)
Sealing material: Silicone rubber (SI)
Main body material: Polyamide Resin (PA6-GF30)
Control stroke range: 0.196-0.98 in (5-25 mm)
Pneumatic Specifications
Pilot air supply range: 43.5~101.5 psi (3~7 bar), specific values
depending on the actuator
Connections: Plug-in hose connector G1/4
Air quality:
Clean dry air, according to ISO 8573-1;
Maximum particle density 10 mg/ ;
Maximum particle size 40 micron;
Maximum oil content 25 mg/m³;
Maximum pressure dew point -4 (-20 °C) or minimum 50 (10
°C) below the lowest operating temperature.;
Air flow rate: 0.60 scfm (17L/min) (input pressure of 87 psi
(0.6Mpa)).

Other manuals for Parker PA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker PA Series and is the answer not in the manual?

Parker PA Series Specifications

General IconGeneral
BrandParker
ModelPA Series
CategoryControl Unit
LanguageEnglish

Related product manuals