For temperature to resistance values when trouble-
shooting probe or temperature issues.
Table 8-21. Temperature – Resistance Values
\
To replace temperature probe, refer to section
8.6.3.
Electrical System Repair Instructions Page 8-32
TEMPERATURE
(°C)
TEMPERATURE
(°F)
RESISTANCE
(OHMS)
-30 -22 111300
-25 -13 86430
-20 -4 67770
-15 5 53410
-10 14 42470
-5 23 33900
0 32 27280
5 41 22050
10 50 17960
15 59 14690
20 68 12090
25 77 10000
30 86 8313
35 95 6940
40 104 5827
45 113 4911
50 122 4160
55 131 3536
Residential Refrigeration
and Front Venting Commercial Refrigeration
Service Manual
STEP 5.
Temperature
Probe
Reverse this instruction to connect the replacement
controller.
8.6.4 Temperature Probe
Each refrigerated zone has one 10K ohm NTC probe,
which senses compartment temperature. Sensing
probe is located behind the control cradle or next to
the evaporator fan behind the cover panel. Defrost
termination probe (evaporator). Additionally, low
temperature products may have a defrost
termination probe inserted into the ns of the
evaporator.
Figure 8-17. Temperature Probe