Appendix
Phone Line Supervision
Elevator Industry REQUIRES notication if phone line is lost
RathSmartPhoneshaveabuilt-inLineCheckFeature.Thephoneconstantlylooksforaphoneline.Whena
phone line is not detected it will trigger the onboard relay. Connect the relay to one of Rath’s alarm devices,
2100-Alarm or OEM versions.
Elevator Code
Phone Line Detection Code Compliant (2.27.1.1.6)
• The Alarm & Junction board provides a simple, fully functional solution to meet the 2010 and 2013 codes
• The Rath Alarm System checks the complete phone line system, from the elevators to the machine room
and from the machine room to the outside world
• Elevator code states each elevator phone needs to check that there is an active phone line at least once
every 24hr period
• If an active phone line is not detected, an audible and visual alarm must be activated at the main landing
panel
•TheSmartPHoneVIandtheAlarm&Junctionboardsprovideafullcircleproductoeringthattakesthe
guesswork out of code compliance
2100-ALARM
Page 11
OEM System: Alarm & Junction