Page #38 background imageLoading...
Page #38 background image
37
Technical Specifications
Model
Rated Output Power 2000W 3000W
Nominal output Voltage RMS
120 VAC ( 100 ~ 120VAC, 5V intervals
Outuput Frequency
50HZ ± 0.3HZ or 60HZ ± 0.3HZ
Output Wave Form
Pure Sine Wave
Output Overload
105% < Load < 120% ± 10% : Fault ( Turn off output after 10 seconds)
120% < Load < 150% ± 10% : Fault ( Turn off output after 3 seconds)
150% < Load ± 10% : Fault ( Turn off output after 1 seconds)
Nominal Input Voltage
12 VDC
Input Voltage Range
10~ 16 VDC ± 0.3 VDC
Low DC Warning Voltage
10.5 VDC ± 0.3 VDC
Low DC Cut-off Voltage
10 VDC ± 0.3 VDC
Short Circuit Protection
No load power Consumption
Software Protection
Nominal Efficiency
> 90% Peak
Nominal Input Voltage
120 VAC
Input Voltage Range
90-138 VAC
Input Frequency Range
40Hz - 70Hz
Input Wave Form
Sine Wave ( Utility or Generator )
Power Factor
0.9 - 1
Optimal Efficiency
>85%
Output Current
5-65A 5-75A
Configu
rable, 5A intervals
Short Circuit Protection
Circuit Breaker
Output Overload
120% < Load < 150% ± 10% : Fault ( Turn off output after 60 seconds)
150% < Load ± 10% : Fault ( Turn off output after 1 second)
Over Charge Protection Shutdown
16.0V for 12VDC
Inverter Specifications
Normal:<20W Normal:<30W
Power Saving:<15W Power Saving:<15W
Surge Power (1 second) 6000W 9000W
3000W 4500W
2400W 3600W
Surge Power (3 seconds)
Surge Power (10 seconds)
R-INVT-PCL1-20111S R-INVT-PCL1-30111S
Charger Specifications