34
COMMISSIONING
boiler is PID modulated to achieve the DHW store setpoint.
DHW store setpoint is manually set on the CH/DHW Setpoints
screen (through the Settings screen).
Ver X.X.XX
Fig. 51
CH/DHW Setpoints
Temperature summary picture of the DHW tank is available on the
DHW screen, accessible through the Tap (faucet) button on the
Boiler screen.
Ver X.X.XX
Fig. 52
Boiler Screen
Ver X.X.XX
Fig. 53
DHW Screen
5.5.1 Minimum Water Flow (Heat Exchanger
Protection)
This unit is self-protected against low water ow. A ow meter
continuously monitors the water ow to each module. If the
water ow decreases below the minimum stated, the burner
automatically shuts off.
9
NOTE: Make sure that the all pumps in the system are free,
bled and rotate in the right direction.
Fig. 54
Minimum Water Flow
5.5.2 Heating System Pressure Test
If the pressure inside the heating circuit falls below the minimum
pressure for the system (7.5 PSI), the appliance switches off and
the 905PB inner display shows “Low water pressure” to indicate
that it is necessary to restore the correct pressure.
Open the lling valve and check the pressure on the temperature/
pressure gauge of Fig. 55.
The error will disappear when the pressure is back at the right
value. To prevent accidental relief valve openings, ll the heating
circuit slowly.
Temperature/Pressure
Gauge
Fig. 55
Temperature/Pressure Gauge location