GENERAL
1 GENERAL
The R Array AR 1000, AR 1500 and AR 2000 MBH Boilers are fully
modulating, high-efciency condensing units. They represent
a true industry advance that meets the needs of today’s energy
and environmental concerns. Designed for application in any
closed loop hydronic system, the modulating capability of the
Array matches energy input directly to uctuating system loads.
The turn down ratio for these models is 10:1 for AR 1000, 15:1 for AR 1500
and 20:1 for AR 2000. These Array models provide extremely
high efcient operation and are ideally suited for modern low
temperature, as well as conventional heating systems.
The Array Models AR 1000, AR 1500 and AR 2000 operate within the
following input and output ranges:
Array
Model
Input Range (BTU/hr.) Output Range (*) (BTU/hr.)
Minimum Maximum Minimum Maximum
AR 1000 100,000 1,000,000 96,100 961,000
AR 1500 100,000 1,500,000 96,100 1,441,500
AR 2000 100,000 2,000,000 96,100 1,922,000
(*) The output of the boiler is a function of the unit’s ring rate,
return water temperature and BTU content of the supplied
gas.
The Array Series of hot water boilers has been designed in
compliance with the CSD-1 code.
When installed and operated in accordance with this Instruction
Manual, these boilers comply with the NOx emission standards
outlined in:
South Coast Air Quality Management District (SCAQMD), Rule 1146.2
Whether used in singular or modular arrangements, the AR 1000,
AR 1500 and AR 2000 offer the maximum venting exibility with
minimum installation space requirements. These Boilers are
Category IV, positive pressure appliances. Single and/or multiple
breeched units are capable of operation in the following vent
congurations:
− Conventional, Vertical Conventional,
− Sidewall Conventional, Direct Vent,
− Vertical Sealed, Direct Vent, Horizontal
These boilers are capable of being vented utilizing PP, CPVC,
Stainless steel AL29-4C and AISI 316L vent systems.
The Array’s advanced electronics include several selectable modes
of operation offering the most efcient operating methods and
energy management system integration.
9
IMPORTANT: Unless otherwise specied, all descriptions and
procedures provided in this Installation & Operation Manual
apply to the Array series of boiler.
9
IMPORTANT: Array boilers are designed for space heating using
hydronic systems. Any different application (like industrial
processes with heavy-duty working conditions) must be
ofcially authorized by
R.
1.1 Warnings & Cautions
Installers and operating personnel MUST, at all times, observe
all safety regulations. The following warnings and cautions
are general and must be given the same attention as specic
precautions included in these instructions.
In addition to all the requirements included in this
R Instruction
Manual, the installation of units MUST conform with local building
codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel
Gas Code Publication No. NFPA-54) for gas-red boilers and ANSI/
NFPASB for LP gas-red boilers.
Where applicable, the equipment shall be installed in accordance
with the current Installation Code for Gas Burning Appliances and
Equipment, CSA B149.1, and applicable Provincial regulations for
the class; which should be carefully followed in all cases.
Authorities having jurisdiction should be consulted before
installations are made.
See pages 7 - 16 - 22 for important information regarding
installation of units within the Commonwealth of Massachusetts.
9
IMPORTANT: This Instruction Manual is an integral part of the
product and must be maintained in legible condition. It must
be given to the user by the installer and kept in a safe place
for future reference.
9
WARNING: Do not use matches, candles, ames, or other
sources of ignition to check for gas leaks.
9
WARNING: Fluids under pressure may cause injury to personnel
or damage to equipment when released. Be sure to shut off
all incoming and outgoing water shutoff valves. Carefully
decrease all trapped pressures to zero before performing
maintenance.
9
WARNING: Before attempting to perform any maintenance on
the unit, shut off all gas and electrical inputs to the unit.
9
WARNING: The exhaust vent pipe of the unit operates under
a positive pressure and therefore must be completely sealed
to prevent leakage of combustion products into living spaces.
9
WARNING: Electrical voltages up to 120 VAC maybe used in
this equipment. Therefore the cover on the unit’s power box
(located behind the front panel door) must be installed at all
times, except during maintenance and servicing.
9
WARNING: Metal casing is an integral part of the boiler. All
panels, doors and seals must be always in place, fully closed,
during boiler’s operation, to prevent any gas or ue leakage
in case of failure.
9
CAUTION: Many soaps used for gas pipe leak testing are
corrosive to metals. The piping must be rinsed thoroughly
with clean water after leak checks have been completed.
0
CAUTION: DO NOT use this boiler if any part has been submerged
under water. Call a qualied service technician to inspect and
replace any part that has been subjected water.