Room probe calibration (the parameter is expressed in eighths of degree)
evaporator probe activation (0=off;1=on)
condenser probe activation (0=off; 1=on)
digital input configuration (0 = open contact, 1 = closed contact)
door open alarm delay time (0 = excluded)
setpoint attivazione resistenza porta (solo se /9 = 0)
door resist. activation adjustment hysteresis (only if /9 =0)
Sensor probe visualisation management (0 = normal, 1 = limited from above r0)
defrost relay defrost management (0 = de-energized when the value set with d2 is reached on the
evaporator, 1 = de-energized at the end of time d7)
defrost/evaporator probe reading
adjuster hysteresis (differential)
min. operating setpoint selectable
max. operating setpoint selectable
compressor activation delay from device start
min. delay between compr. stop and subsequent start
compressor start cycle time in the event of room probe alarm
C5 % where compr. starts in the event of room probe alarm
defrost interval (0= excluded)
defrost type (0= resistance, 1= hot-gas)
end-of-defrost temp. (relating to evaporator temper.)
max. defrost duration (0 = the defrosting function will not start; 255 = the defrosting function will go
on continuously)
defrosting display (0=actual cell temperature, 1=stopped cell temperature, 2=dEF label)
defrost interval count: 0= actual hours; 1=hours comp. ON; 2= autodeterm.
alarm hysteresis (differential)
min. operating setpoint alarm (0= excluded)
max. operating setpoint alarm (0= excluded)
alarm exclusion from device start
buzzer activation mode for alarm : 0= always; 1= timer-controlled
time limit for buzzer acoustic signal (only if A4 = 1)
temperature alarm exclusion time (only if A1 and/or A2 0)
temp. alarm exclusion time after evap. stop (for A1 and/or A2 0)
ADJUSTING THE EVAPORATOR AND CONDENSER VANS
temper. above which the evap. fan stops ( only if /A = 1 and F7 = 3 or 4)
fan differential (relating to F1, only if /A = 1 and F7 = 3 or 4)
evaporator fan func. during regular operation (0=OFF; 1=ON; 2=parallel with compressor;
3=determined by F1 and F2 with comp. ON and OFF with comp. OFF
evap. vent. operation during defrost and dripping (0= OFF, 1= ON, 2= determ. with F7)
evaporator fan stop after dripping
temperature below which the condenser fan turns off
condenser fan differential (relating to F6)
condenser fan func. during regular operation (0=parallel with compr.; 1=ON); also refer to F6 and F7
condenser fan func. during defrost and dripping (0=OFF; 1=ON, 2=ON if Tc≥26°C and OFF if
Tc<25°C)
critical temperature for signalling high condensation temperature
critical temperature for condenser dirty alarm
time the condenser probe stays on the value equal or higher than FA for activation of the HtC alarm
time the condenser probe stays on the value equal or higher than Fb for activation of the dCA alarm
temperature increase on the device set point value in case of an active dCA alarm
critical temperature for high pressure alarm
time limit used to pass from the FA value to the Fb value, within which the HP alarm is however
activated
critical temperature for signalling low evaporation temperature