9. MAINTENANCE VM-5S
-63-
9-2-2 VERIFICATION OF OPERATION
(1) Verification of Alarm Operation (No output)
Connect the input transducer. Verify that the OK lamp lights at the end of the POWER ON
TIMER period.
At the same time, test the OK contact points for continuity.
(2) Verification of Alarm Operation (Output)
Disconnect the signal transmission cable of the input transducer from the output terminal block.
Verify that the OK lamp lights at the end of the POWER ON TIMER period.
At the same time, test the OK contact points for continuity.