Technical data of CPU 31x
7.7 CPU 317-2 PN/DP
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
7-39
Technical Data
2nd interface
Type of interface PROFINET
Physics Ethernet
electrically isolated Yes
Autosensing (10/100 Mbps) Yes
Functionality
PROFINET
Yes
MPI
No
PROFIBUS DP
No
Point-to-point connection
No
Services
PG communication
Yes
OP communication
Yes
S7 communication
Max. configurable connections
Maximum number of instances
Yes (with loadable FBs)
16
32
Routing
Yes
PROFINET IO
Yes
PROFINET CBA
Yes
PROFINET IO
Number of integrated PROFINET IO controllers 1
Number of connectable PROFINET IO devices 128
Max. user data consistency with PROFINET IO 256 bytes
Update Time 1 ms to 512 ms
The minimum value is determined by the set
communication portion for PROFINET IO, the
number of IO devices and the amount of
configured user data.
S7 protocol functions
PG functions
Yes
OP functions
Yes
Open IE communication via TCP/IP
Yes
GSD file The latest GSD file is available at:
http://www.automation.siemens.com/csi/gsd
Programming
Programming language LAD/FBD/STL
Available instructions See the Instruction List
Nesting levels 8
System functions (SFCs) See the Instruction List
System function blocks (SFBs) See the Instruction List
User program security Yes

Table of Contents

Other manuals for Siemens CPU 314

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 314 and is the answer not in the manual?

Siemens CPU 314 Specifications

General IconGeneral
BrandSiemens
ModelCPU 314
CategoryController
LanguageEnglish

Related product manuals