EasyManuals Logo

Siemens LMV52.200A2 User Manual

Siemens LMV52.200A2
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
31/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 3 Fuel train applications (examples) 13.08.2004
HO
IV1V2V3
ts 1
ts 2
Operation
Air damper
position
V3 (= stage 2)
Multistage operation
7550f01cE/0200
MIN
MAX
Heavy oil
(direct trafo ignition)
Phase 38
max. 45 s
**)
Modulating burner
Circulation from Phase 38, max. 45 s
as soon as direct heavy oil start
= ON in Phase 38:
→ Phase change in Phase 40
Direct heavy oil start = OFF
at the end of Phase 38
→ Repetition (max. 3 times in total)
Gas trains G, Gp1 and Gp2
1)
can be randomly combined with oil trains LO and HO for
operation with dual-fuel burners since these fuel trains operate independently.
Oil trains LOgp and HOgp are designed for ignition with a gas pilot. They
must always be combined with a special gas train Gp2 for operation with a
dual-fuel burner.
1) With Gp2 permitted with
HW 01.C0 and SW V01.40 or higher
Fuel valve
control program
Note on dual-fuel burners