Certification
6.1.7 Other Approvals
6.1.7 Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RX1512 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test Description Test Levels Severity
Levels
Enclosure Contact ± 8 kVIEC 61000-4-2 ESD
Enclosure Air ± 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m
Signal ports ± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV 4
Signal ports ± 2 kV Line-to-Ground
± 2 kV Line-to-Line
4IEC 61000-4-5 Surge
DC Power Ports ± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
Signal ports
DC Power Ports
IEC 61000-4-6 Induced (Con-
ducted) RFI
Earth ground ports
10 V 3
100 A/m, continuous
1000 A/m for 1 s
Note
a
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s 5
Signal portsIEC 61000-4-12 Damped Oscillatory
DC Power Ports
2.5 kV common, 1 kV dif-
ferential mode @1 MHz
3
Signal portsIEC 61000-4-16 Mains Frequen-
cy Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
40
RUGGEDCOM RX1512
Installation Manual, 07/2019, C79000-G8976-1057