6.2EMC and Environmental Type Tests
Description Test Levels
Signal ports 2 kV
DC Power Ports 1.5 kV
Dielectric Strength
AC Power Ports 2 kV
Signal ports ± 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Fast Transient
Earth ground ports
± 4 kV
Signal ports 2.5 kV common mode @1MHz
DC Power Ports
Oscillatory
AC Power Ports
2.5 kV common
1 kV differential mode @ 1 MHz
Radiated RFI Enclosure ports 35 V/m
Enclosure Contact ± 8 kVESD
Enclosure Air ± 15 kV
Environmental Type Tests
Test Description Test Levels Severity
Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Db 95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-2-78 Humidity (Damp Heat, Steady State) 10 days at 40 °C
(104 °F) and 93%
relative humidity
(non-condensing)
IEC 60068-2-14 Change of Temperature 5 cycles at -40 to 85 °C
(-40 to 185 °F) and 3
hour dwells at rate of
1 °C/min (1.8 °F/min)
IEC 60255-21-1 Vibration 2 g @ 10-150 Hz Class 2
Shock 30 g @ 11 ms Class 2IEC 60255-21-2
Bump 10 g @ 16 ms Class 1
IEC 60255-21-3 Seismic Method A Level 2
IEC 60529 Ingress Protection IP4x
Military Standard Tests
Test Description Test Levels
MIL-STD-810G Altitude 12192 m (40000 ft) @ 40 °C, 90
minutes
54
RUGGEDCOM RX1524
Installation Manual, 04/2021, C79000-G8976-1487-02