Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Instructions:
1. Step 1: Set P0003=3 (expert user)
2. Step 2: Go to P0013 indices 0 to 16 (user list)
3. Step 3: Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following
values are fixed and cannot be changed:
- P0013 index 19=12 (key for user defined parameter)
- P0013 index 18=10 (commissioning parameter filter)
- P0013 index 17= 3 (user access level)
4. Step 4: Set P0003=0 to activate the user defined parameter.
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set
P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view
other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note:
Alternatively, set P0010=30 (commissioning parameter filter=factory setting) and P0970=1 (factory reset) to perform a
complete factory reset. The default values of P0011 ("lock") and P0012 ("key") are the same.
r0018 Firmware version
Displays version number of installed firmware.
Unit: - Min: - Def: - Max: -
Level 3
r0019 CO/BO: BOP control word
Displays status of operator panel commands.
The settings below are used as the "source" codes for keypad control when connecting to
BICO input parameters.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 ON/OFF1 0 NO, 1 YES
Bit01 OFF2: Electrical stop 0 YES, 1 NO
Bit08 not used 0 NO, 1 YES
Bit11 not used 0 NO, 1 YES
Bit12 Hand Operation 0 NO, 1 YES
Bit13 Motor potentiometer MOP up 0 NO, 1 YES
Bit14 Motor potentiometer MOP down 0 NO, 1 YES
Bit15 Auto Operation 0 NO, 1 YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the
relevant command.
The following functions can be "connected" to individual buttons:
- ON/OFF1 - JOG - INCREASE
-OFF2 -REVERSE -DECREASE
r0020 CO: Act. frequency setpoint
Displays actual frequency setpoint (output from ramp function generator).
Unit: Hz Min: - Def: - Max: -
Level 3
r0021 CO: Act. frequency
Displays actual variable speed drive output frequency (r0024) excluding slip compensation,
resonance damping and frequency limitation.
Unit: Hz Min: - Def: - Max: -
Level 3
r0022 Act. rotor speed
Displays calculated rotor speed based on variable speed drive output frequency [Hz] x 120 /
number of poles.
Unit: 1/min Min: - Def: - Max: -
Level 3
Note:
This calculation makes no allowance for load-dependent slip.
r0024 CO: Act. output frequency
Displays actual output frequency (slip compensation, resonance damping and frequency
limitation are included).
Unit: Hz Min: - Def: - Max: -
Level 3
r0025 CO: Act. output voltage
Displays [rms] voltage applied to motor.
Unit: V Min: - Def: - Max: -
Level 3
r0026[2] CO: Act. DC-link voltage
Displays DC-link voltage.
Unit: V Min: - Def: - Max: -
Level 3
r0027 CO: Act. output current
Displays [rms] value of motor current [A].
Unit:A Min:- Def:- Max:-
Level 3
r0031 CO: Act. torque
Displays motor torque.
Unit: Nm Min: - Def: - Max: -
Level 3
r0032 CO: Act. power
Displays motor power.
Unit: - Min: - Def: - Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).

Table of Contents

Other manuals for Siemens SED2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SED2 Series and is the answer not in the manual?

Siemens SED2 Series Specifications

General IconGeneral
BrandSiemens
ModelSED2 Series
CategoryInverter
LanguageEnglish

Related product manuals