Introduction
1.1 Important notes
SIMOCODE pro
10 System Manual, 05/2019, A5E40507475002A/RS-AD/004
Device series
When reference is made to "SIMOCODE pro", the reference also includes the following
device series:
SIMOCODE pro C (see Device series (Page 24))
SIMOCODE pro S (see Device series (Page 24))
SIMOCODE pro V PB (PROFIBUS) (see Device series (Page 24))
SIMOCODE pro V PN (PROFINET) (see Device series (Page 24))
SIMOCODE pro V PN GP (PROFINET) (see Device series (Page 24))
SIMOCODE pro V MR (Modbus RTU) (see Device series (Page 24))
SIMOCODE pro V EIP (EtherNet/IP) (see Device series (Page 24))
When reference is made to "SIMOCODE pro V", the reference also includes all pro V
devices, independently of communication.
SIMOCODE pro response tables
Specific responses (deactivated, signaling, warning, tripping) can be parameterized for
various SIMOCODE pro functions, such as overload. These are always displayed in tabular
form:
"X" = Applicable
"—" = not applicable
Default values are marked "d" for "default" in parentheses.
Response
Function 1
Function 2
Function 3
Tripping
X (d)
X
Warning X (d) X
Signaling
X
X
Deactivated
X
X
X (d)
Delay
0 to 25.5 s (default: 0)
Short description of the responses:
Tripping: The contactor controls QE* are tripped. A fault message is generated which is
available as diagnostics via the communication bus. The fault message and the
device-internal signal remain on until the appropriate length of time has elapsed or the
cause of the fault has been eliminated and acknowledged.
Warning: In addition to the device-internal signal, a warning signal is generated that is
available as diagnostics via the communication bus.
Signaling: Only a device-internal signal is generated, which can be further processed as
required.
Deactivated: The appropriate function is switched off, no signals are generated.
A delay time can also be set for specific responses.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro V PB and is the answer not in the manual?

Siemens SIMOCODE pro V PB Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro V PB
CategoryControl Unit
LanguageEnglish

Related product manuals