Installation
SIMODRIVE base line A Start-Up 2-21
Fuse/circuit Fuse of linear circuit breaker must be used which are designed to protect
breaker the line supply feeder cables. We recommend the SIEMENS fuse type
listed below:
I
rated
16A;
I
fuse
0.2s >70A;
I
fuse
4S
> 50A;
I
fuse
10s
> 42A;
I
fuse
240s
> 30A;
The order number of the recommended SIEMENS fuse is
16AD01 Neoz./B.No.5SE2116
Or you can choose SIEMENS circuit breaker: 3RV1031-4BA10.
Isolating SIMODRIVE base line A can be connected directly to TN-C line supply
transformer system. The isolating transformer is used as an option in this line supply
type. The connecting diagram is shown in the Fig.2-10. But the isolating
transformer must be used in following cases:
1. IT line supply system or TT line supply system;
2. The touchable part in the equipment has potential because of the
unequilibrium load current or harmonic current in three-phase
system in TN line supply
3. Upstream devices providing protection against hazardous leakage
currents or for fire protection doesn’t comply with the requirements
of DIN EN 50178