11.98 Connection
Siemens AG 67087-6AC85-0AA0 ENGLISH
3-3
Common Rectifier Operating instructions
Unit order No. Mains supply cable fuses
Column 1 Column 2 Column 3
Siemens gR
(SITOR)
Preferred type
Siemens (SITOR) Bussmann
US-standard
6SE70 A Type A Type A Type
24-1EB85-0AA0 63 3NE4118 63 170M3610
28-6EC85-0AA0 80 3NE1820-0 125 3NE3222 125 170M3613
24-1FB85-0AA0 63 3NE4118 63 170M3690
27-2FC85-0AA0 80 3NE1820-0 125 3NE3222 100 170M3692
28-8FC85-0AA0 100 3NE1021-0 125 3NE3222 160 170M3693
Table 3.2 Recommended mains fuses
Column 1: This fuse with gR characteristic protects the semiconductors. At the same time, they also have
line protection characteristic which can be used if the appropriate conductor cross-sections are
chosen, e.g. in accordance with DIN VDE 0100 Part 430 (to be applied for preference).
Column 2, 3: Semiconductor protection only, lines are not reliably protected. Discriminative line protection is
assured only by correlating the line protection fuses to the installed conductor cross-section in
accordance with the applicable regulations - e.g. DIN VDE 0100 Part 430.
Unit order No. Rated input- Commutation choke 2 %
voltage current Type Voltage / Frequency Rated current
6SE70 (V) (A) (V / Hz) (V / Hz) (A)
24-1EB85-0AA0 200 to 480 36 4EP3700-2UK 400 / 50 460 / 60 35,5
28-6EC85-0AA0 200 to 480 74 4EP3900-2UK 400 / 50 460 / 60 80
24-1FB85-0AA0 500 to 600 36 4EP3700-1UK 500 / 50 35,5
27-2FC85-0AA0 500 to 600 62 4EP3900-1UK 500 / 50 63
28-8FC85-0AA0 500 to 600 82 4EP4000-1UK 500 / 50 80
Table 3.3 Recommended commutation choke