..C4 Quick Start Guide..
2
1. Navigate to MAIN MENU.
2. Go to DEBUG.
3. Go to EDIT PARAMETERS.
4. Go to HEX FORMAT.
5. Select BIT 1 [indicated as ‘01’ on the LCD].
6. Set the ADDRESS to 0131.
7. Set the PARAMETER to ON.
1.4 Normal Terminal Stop Bypass
If the elevator is running at a lower speed, usually 10 FPM, than the Inspection Speed requested by the
controller, it could be that the Normal Terminal Stop (NTS) device is active.
To bypass the NTS feature during Construction Mode, turn ON DIP B1 to invert the NTS output to drive.
NOTE: it may not always be possible to bypass the NTS using the B1 DIP. An Alternative method is as
follows:
Magnetek drives:
- Congure (C0) -> Logic Inputs (C2) -> NTSD Input 1 -> set function to NO. Remember to
revert back after Construction mode is completed.
KEB drives:
- Input -> Input 1 Function (LI04) -> set to 21 (Emergency Slowdown (ESD)).
1.5 Running the Car on Construction Mode
On Construction Mode, most things are either suppressed or bypassed. As such, the controller must not
exhibit any faults; however, if the controller has an active fault, red LED(s) will illuminate.
To Check for faults, follow this procedure:
1. Navigate to MAIN MENU.
2. Go to FAULTS.
3. Go to ACTIVE FAULTS.
See the Fault and Alarm Manual for C4 controllers.
If no active faults are detected, a zero-speed test is recommended to verify that the brakes are receiving
the right picking voltage.
To perform a zero-speed test, follow this procedure:
1. Navigate to MAIN MENU.
2. Go to SETUP.