Page #29 background imageLoading...
Page #29 background image
-28-
No.EX##-OMN0036
Specification
Specifications
Model EX600-DXPB EX600-DXNB
EX600-DXPC EX600-DXNC
EX600-DXPD EX600-DXND
Input type PNP NPN PNP NPN PNP NPN
Input connector M12 (5 pin) socket
1
M8 (3 pin) socket M12 (5 pin) socket
1
Number of inputs
8 inputs
(2 inputs/connector)
8 inputs
(1 input/connector)
16 inputs
(2 inputs/connector)
Powor supply
voltage
(Control and input)
24 VDC Class2, 2 A
Max. sensor
supply current
0.5 A/ connector
2 A/unit
0.25 A/ connector
2 A/unit
0.5 A/ connector
2 A/unit
Protective function Short circuit protection
Input resistance 2.7 k
Rated input current 9 mA or less
ON voltage
/ON current
17 V or more/5 mA or more
(NPN input: between input terminal and +24 V)
(PNP input: between input terminal and 0 V)
OFF voltage
/OFF current
5 V or less/1 mA or less
(NPN input: between input terminal and +24 V)
(PNP input: between input terminal and 0 V)
2-wire - 0.5 mA/input
2
-
Input specifications
Open
circuit
detection
current
3-wire - 0.5 mA/Connector
2
-
Current consumption 50 mA or less 55 mA or less 70 mA or less
Enclosure IP67 (With manifold assembled)
3
Operating
temperature range
-10 to 50
o
C
4
Storage
temperature range
-20 to 60
o
C
Operating humidity
range
35 to 85%RH (No condensation)
Withstand voltage 500 VAC for 1 minute between external terminals and FE
Insulation
resistance
500 VDC, 10 M or more between external terminals and FE
Vibration
resistance
10 to 57 Hz: constant amplitude 0.75 mm p-p
57 to 150 Hz: constant acceleration 49 m/s
2
for 2 hours each in direction X, Y and Z respectively (De-energized)
Impact resistance 147 m/s
2
3 times each in directions of X, Y and Z respectively (De-energized)
Environment
Pollution degree Pollution degree 2 (UL508)
Standard CE marking, UL(CSA), RoHS
Weight 300 g 275 g 340 g
∗1: An M12 connector (4 pin) can also be connected.
2: Available only for EX600-DX C1.
3: All unused connectors must have a seal cap fitted.
4: The UL compliant temperature is 0 to 50
o
C.