Other Settings
Peak/Bottom value display
The maximum (minimum) pressure from when the power was supplied to this moment is detected and
updated.
In peak/bottom display mode, this pressure is displayed.
For peak display, when the
button is pressed for 1 second or longer, the maximum pressure and "Hi"
starts flashing, and is held.
To release holding the display of the maximum pressure, press the
button for 1 second or longer again
to return to measurement mode.
For bottom display, when the
button is pressed for 1 second or longer, the minimum pressure and "Lo"
starts flashing and is held.
To release holding the display of the minimum pressure, press the
button for 1 second or longer again
to return to measurement mode.
If the
and buttons are pressed simultaneously for 1 second or longer while the pressure is being
held, the maximum (minimum) valus are reset.
Zero Clear
The displayed value can be adjusted to zero when the measured pressure is within 10% of the span
between atmospheric pressure and upper limit of rated pressure range, from the default value of pressure.
(A tolerance range of ±1% digit may apply due to individual product differences).
Press the
and buttons simultaneously for 1 second or longer, to clear the display to “0”.
The display will return to measurement mode automatically.
For analogue output, the analogue output will be changed along with the display.
Key Lock
The key lock function is used to prevent errors occurring due to unintentional changes of the set values.
If a button operation is performed while the key lock setting is ON, "LoC" is displayed for approximately 1
second.
The set value can be displayed by pressing the
button (It cannot be changed).
<Operation - Without security code input- >
1, Press the
button for 5 seconds or longer in measurement mode.
The current setting "LoC" or "UnL" is displayed.
(selecting or releasing the key lock is carried out in a similar way).
2, Press the
or button to select key lock (or key unlock).
3, Press the
button to store the setting.

Questions and Answers: